Hybrid Emergency Control Devices

In this section, there are four modes which allow users to switch the status of the emergency device and start the function test and duration test manually for all the emergency devices on the network level.

Koolmesh app also lists out all the emergency devices by zone in this network which enable users to check the emergency logs and status and current status individually. Users also can schedule the self-test according to the application.

E1

● Resume to normal mode: When the luminaries are in emergency mode, then users can use this function to manually switch the emergency mode to the normal mode.

● Enter inhibit mode:
Activated inhibit mode makes it possible to set the emergency mode to "inhibited"; in this mode, the power can be turned off without switching to emergency mode. Normally it is for maintenance purposes, if the maintenance and inspection is needed on site, users can use this function to prevent the luminaries from switching to emergency mode. Users can use this function to activate it manually by selecting how long they would like to stay in inhibit mode, the longest time being 180H 59min.

● Function test :
This button enables users to carry out the function test manually. When the maintenance team on site they can use this function to start the test to check the health of battery. But users still need to select the start time and the time period for battery discharge, the longest testing period for battery discharge is 1H 59min.

● Duration test:
This button enables users to carry out the duration test manually. When the maintenance team on site they can use this function to start the duration test. But user still need to select the start time and end time, users can start the test immediately or until fully charged. There is no limitation for the minimum and maximum testing period, just for testing convenience when users want to have a quick check. The shortest time can be 10s, the longest testing period is 45H 30min for emergency duration test. Please choose a suitable duration period according to the battery’s capacitance. If the duration time is set too long, the system may judge battery capacity to fail due to the battery failing to last for the preset period.

Users can click the devices they would like to set in the emergency list, like HBEM01. Koolmesh app will list out all the detail information about this emergency device.

1.Emergency logs which enable users to check all the logs of this emergency device, including the results of monthly test and annual test, also the emergency fault records enable users to make a remark and signature.

※ Click "remarkNone@3x" to make the remark, then the remark will be presented together with account and time right below the record. After finished the remark, the grey icon "remarkNone@3x" will become balck"remarkDone@3x" .

All those records and remarks also will be presented in the Emergency report, users can review all these via login the web platform.

E2 E3 E4

For the Fault records, there are safeguard, rectification and confirm available for different person in charge, the “confirm” will only be available when the action and signature make by “safeguard” and “rectification”.

All those records and remarks also will be presented in the Emergency report, user can review all these via login the web platform.

2.Extended emergency time which means when main power is present but was recently off , so the lamp continues to be operated in the same way as in emergency mode for a period of time, or until the battery is discharged. The longest time can be 23H 59min 59S. It is useful to extend the emergency time when the main power is resumed after suffering from a power failure. It can prevent sudden power failure happening again due to an unstable period which could cause the luminaries flickering.

3.Emergency duration time setting which are to check the battery level conditions. The longest testing period for emergency duration is 15H. When users set the emergency duration time, please choose a suitable testing period according to the battery’s capacitance. If the duration testing period is set too long, the system may judge battery capacity to fail due to that battery failing to last for the preset period.

4.Self-test scheduling which Koolmesh app will list out the schedule by month, user can set every month according to real application for “Function test”and “Duration test ”.Diferent function has diferent color, “Function test” is grey; “Duration test” is orange. User can select a certain date and hours for self-test.

E5 E6

※ During the function and duration test, if there is any emergency fault found, the system will send the emergency fault notifcation immediately. Users can check the details by refreshing “Emergency logs” or email (set the auto-notifcation in the web platform in advance).

※ After fnished all the test, users can check the result via refresh “Emergency logs”. Or users can check the report by Koolmesh web platform (www.iot.koolmesh.com, same account and password with Koolemsh app).System also will send the report to the registered email address where are users already set the auto-notifcation in the web platform in advance.